NF C 15-100 voltage drop calculator
Enter the current, the one-way length and the cross-section; the calculator below returns the drop in volts and percent and a PASS or FAIL against 3 % for lighting and 5 % for other circuits under NF C 15-100, with NF C 15-100 §525 cited under the number.
Limits and citations come from the app's pack files. The calculator below is checked against the app's engine on every build · engine 1, built 2026-11-14.
voltage drop 6.2 percent, fail, limit 5 percent other
Working
- Resistance
- r₂₀ = 7.410 Ω/km · Copper 2.5 mm² · IEC 60228 max DC
- Temperature
- θ = 70 °C (PVC 70 °C operating) · α = 0.00393 /K · rθ = 8.866 mΩ/m
- Formula
- ΔU = 2 · I · L · rθ · cos φ
- Numbers
- 2.000 · 16.00 A · 50.0 m · 8.866 mΩ/m · 1.00 = 14.186 V
- Percent
- 14.186 / 230 = 6.17 % · limit 5 % · NF C 15-100 (FR) pack
- Not checked
- Iz · short-circuit · Zs / disconnection time
- Engine
- 1
Design aid. Verify against your installation standard and manufacturer data.
Same numbers. Offline. In your pocket.
In the app, one tap tries the next size.
The app does this in the van with no signal, keeps your last five jobs, and sizes the cable for you with Iz and voltage drop together.
Finding the smallest size for you is Pro. What Pro unlocks
Checked against the app's engine on every build · engine 1
The limits in the NF C 15-100 pack
Straight from the app's pack file. The citation is what the app prints under every result.
| Pack | Lighting | Other | Cited as |
|---|---|---|---|
| NF C 15-100 (FR) | 3 % | 5 % | NF C 15-100 §525 |
How the app applies NF C 15-100
NF C 15-100 is the French standard for low-voltage installations, published by AFNOR and built on the international IEC 60364 series. Its voltage drop requirement is §525, and the app cites it by clause: the line under every result names §525 and the row it used.
- Lighting and other circuits, public supply. The pack holds both rows for an installation fed from the public network; pick the one that matches the circuit and the verdict and citation follow it.
- Operating temperature, not 20 °C. The conductor resistance is taken at the temperature the cable runs at under load: 70 °C for PVC, 90 °C for XLPE. A calculation at 20 °C under-reads the drop and can pass a cable that fails.
- Single-phase and three-phase. 230 V single-phase and 400 V three-phase, plus DC for 12, 24 and 48 V work.
- A custom limit is one tap away for a private substation or a stricter specification.
The figures and citations on this page come from the app’s NF C 15-100 pack file, the same file the app reads on site.
Worked example
| System | 230 V single-phase |
|---|---|
| Load | 16 A |
| Length, one way | 50 m |
| Cross-section | 2.5 mm² copper, PVC at 70 °C |
| Limit | NF C 15-100 §525 — voltage drop, other circuits 5 % |
r20 for 2.5 mm² is 7.41 Ω/km; at 70 °C that is 8.87 mΩ/m. ΔU = 2 × 16 × 50 × 0.00887 = 14.19 V, which is 6.17 % of 230 V. FAIL at 5 %, over by 1.2 %, with 215.8 V at the load. One size up, 4 mm², comes to 3.8 %. The app's working card shows exactly this.
Solve for length
Switch “Solve for” to Max length and the same formula runs backwards: with 16 A on 2.5 mm² at 5 % you can go 40.5 m one way.
Questions
Single-phase or three-phase — what changes?
The formula. Single-phase and DC count the run twice, out and back (ΔU = 2 · I · L · r); three-phase uses √3 instead of 2 and works on the line-to-line voltage. The percentage is taken of the nominal voltage of the system you pick.
My installation has its own HV/LV substation. Which limit applies?
The pack holds the rows for a supply from the public low-voltage network: 3 % for lighting and 5 % for other circuits under NF C 15-100. The standard allows more for an installation fed from its own substation; type the figure from your edition as a custom limit.
Does the limit apply to the final circuit alone?
No. §525 sets the drop from the origin of the installation to the point of use, so a sub-distribution board and the circuits it feeds share one budget. Work out each run and add them.
Other standards
- BS 7671 voltage drop
- NEN 1010 voltage drop
- DIN VDE 0100 voltage drop
- NF C 15-100 voltage drop
- IEC 60364 voltage drop
The voltage drop page: formula, operating temperature, and every pack side by side →