NF C 15-100 voltage drop calculator

Enter the current, the one-way length and the cross-section; the calculator below returns the drop in volts and percent and a PASS or FAIL against 3 % for lighting and 5 % for other circuits under NF C 15-100, with NF C 15-100 §525 cited under the number.

Limits and citations come from the app's pack files. The calculator below is checked against the app's engine on every build · engine 1, built 2026-11-14.

voltage drop 6.2 percent, fail, limit 5 percent other

14.2V
6.2%
FAIL
Over limit by 1.2 % · 215.8 V at the load
NF C 15-100 §525 — voltage drop, other circuits 5 %
Working
Resistance
r₂₀ = 7.410 Ω/km · Copper 2.5 mm² · IEC 60228 max DC
Temperature
θ = 70 °C (PVC 70 °C operating) · α = 0.00393 /K · rθ = 8.866 mΩ/m
Formula
ΔU = 2 · I · L · rθ · cos φ
Numbers
2.000 · 16.00 A · 50.0 m · 8.866 mΩ/m · 1.00 = 14.186 V
Percent
14.186 / 230 = 6.17 % · limit 5 % · NF C 15-100 (FR) pack
Not checked
Iz · short-circuit · Zs / disconnection time
Engine
1

Design aid. Verify against your installation standard and manufacturer data.

Try it

Free tier · same numbers as the app
Solve for
System
m one-way
CSA
2.5 mm²
Conductor
Insulation
cos φ
Limit

Conductor at operating temperature (70 °C). Values commit when you leave a field, as in the app.

Same numbers. Offline. In your pocket.

In the app, one tap tries the next size.

The app does this in the van with no signal, keeps your last five jobs, and sizes the cable for you with Iz and voltage drop together.

Finding the smallest size for you is Pro. What Pro unlocks

Checked against the app's engine on every build · engine 1

The limits in the NF C 15-100 pack

Straight from the app's pack file. The citation is what the app prints under every result.

PackLightingOtherCited as
NF C 15-100 (FR)3 %5 %NF C 15-100 §525

How the app applies NF C 15-100

NF C 15-100 is the French standard for low-voltage installations, published by AFNOR and built on the international IEC 60364 series. Its voltage drop requirement is §525, and the app cites it by clause: the line under every result names §525 and the row it used.

  • Lighting and other circuits, public supply. The pack holds both rows for an installation fed from the public network; pick the one that matches the circuit and the verdict and citation follow it.
  • Operating temperature, not 20 °C. The conductor resistance is taken at the temperature the cable runs at under load: 70 °C for PVC, 90 °C for XLPE. A calculation at 20 °C under-reads the drop and can pass a cable that fails.
  • Single-phase and three-phase. 230 V single-phase and 400 V three-phase, plus DC for 12, 24 and 48 V work.
  • A custom limit is one tap away for a private substation or a stricter specification.

The figures and citations on this page come from the app’s NF C 15-100 pack file, the same file the app reads on site.

Worked example

System230 V single-phase
Load16 A
Length, one way50 m
Cross-section2.5 mm² copper, PVC at 70 °C
LimitNF C 15-100 §525 — voltage drop, other circuits 5 %

r20 for 2.5 mm² is 7.41 Ω/km; at 70 °C that is 8.87 mΩ/m. ΔU = 2 × 16 × 50 × 0.00887 = 14.19 V, which is 6.17 % of 230 V. FAIL at 5 %, over by 1.2 %, with 215.8 V at the load. One size up, 4 mm², comes to 3.8 %. The app's working card shows exactly this.

Solve for length

Switch “Solve for” to Max length and the same formula runs backwards: with 16 A on 2.5 mm² at 5 % you can go 40.5 m one way.

What this does not check. Current-carrying capacity (Iz) — use the ampacity or cable size calculator; loop impedance and disconnection time; short-circuit withstand; the drop before the origin of the installation. Lastsocket is a design aid. It does not replace the applicable installation standard, manufacturer data, or a qualified person’s judgement. Sources and limits →
Free or Pro. Typing a cross-section and reading the verdict is free, in every pack, with one "try the next size" tap on a FAIL. Finding the smallest cross-section automatically is Pro.

Questions

Single-phase or three-phase — what changes?

The formula. Single-phase and DC count the run twice, out and back (ΔU = 2 · I · L · r); three-phase uses √3 instead of 2 and works on the line-to-line voltage. The percentage is taken of the nominal voltage of the system you pick.

My installation has its own HV/LV substation. Which limit applies?

The pack holds the rows for a supply from the public low-voltage network: 3 % for lighting and 5 % for other circuits under NF C 15-100. The standard allows more for an installation fed from its own substation; type the figure from your edition as a custom limit.

Does the limit apply to the final circuit alone?

No. §525 sets the drop from the origin of the installation to the point of use, so a sub-distribution board and the circuits it feeds share one budget. Work out each run and add them.

Other standards

The voltage drop page: formula, operating temperature, and every pack side by side →