DIN VDE 0100 voltage drop calculator

Enter the current, the one-way length and the cross-section; the calculator below returns the drop in volts and percent and a PASS or FAIL against 3 % for every circuit under DIN VDE 0100, with the rule it applies cited under the number.

Limits and citations come from the app's pack files. The calculator below is checked against the app's engine on every build · engine 1, built 2026-11-14.

voltage drop 3.7 percent, fail, limit 3 percent other

8.5V
3.7%
FAIL
Over limit by 0.7 % · 221.5 V at the load
DIN 18015-1 — voltage drop, other circuits 3 % from the meter (residential)
Working
Resistance
r₂₀ = 7.410 Ω/km · Copper 2.5 mm² · IEC 60228 max DC
Temperature
θ = 70 °C (PVC 70 °C operating) · α = 0.00393 /K · rθ = 8.866 mΩ/m
Formula
ΔU = 2 · I · L · rθ · cos φ
Numbers
2.000 · 16.00 A · 30.0 m · 8.866 mΩ/m · 1.00 = 8.511 V
Percent
8.511 / 230 = 3.70 % · limit 3 % · DIN VDE 0100 (DE) pack
Not checked
Iz · short-circuit · Zs / disconnection time
Engine
1

Design aid. Verify against your installation standard and manufacturer data.

Try it

Free tier · same numbers as the app
Solve for
System
m one-way
CSA
2.5 mm²
Conductor
Insulation
cos φ
Limit

Conductor at operating temperature (70 °C). Values commit when you leave a field, as in the app.

Same numbers. Offline. In your pocket.

In the app, one tap tries the next size.

The app does this in the van with no signal, keeps your last five jobs, and sizes the cable for you with Iz and voltage drop together.

Finding the smallest size for you is Pro. What Pro unlocks

Checked against the app's engine on every build · engine 1

The limits in the DIN VDE 0100 pack

Straight from the app's pack file. The citation is what the app prints under every result.

PackLightingOtherCited as
DIN VDE 0100 (DE)3 %3 %DIN 18015-1

How the app applies DIN VDE 0100

DIN VDE 0100 is the German series for low-voltage installations, built on the international IEC 60364 series. For voltage drop in homes, German practice applies DIN 18015-1, measured from the meter, and that is the rule the pack holds and cites: the line under every result names DIN 18015-1.

  • One figure from the meter. The pack’s rule does not split lighting from other circuits, so the limit is the same whichever row you pick. The budget covers everything after the meter: add the drop of a sub-main to the circuit it feeds.
  • Operating temperature, not 20 °C. The conductor resistance is taken at the temperature the cable runs at under load: 70 °C for PVC, 90 °C for XLPE. A calculation at 20 °C under-reads the drop and can pass a cable that fails.
  • Single-phase and three-phase. 230 V single-phase and 400 V three-phase, plus DC for 12, 24 and 48 V work.
  • A custom limit is one tap away for commercial jobs where a different figure is agreed.

The figures and citations on this page come from the app’s DIN VDE 0100 pack file, the same file the app reads on site.

Worked example

System230 V single-phase
Load16 A
Length, one way30 m
Cross-section2.5 mm² copper, PVC at 70 °C
LimitDIN 18015-1 — voltage drop, other circuits 3 % from the meter (residential)

r20 for 2.5 mm² is 7.41 Ω/km; at 70 °C that is 8.87 mΩ/m. ΔU = 2 × 16 × 30 × 0.00887 = 8.51 V, which is 3.70 % of 230 V. FAIL at 3 %, over by 0.7 %, with 221.5 V at the load. One size up, 4 mm², comes to 2.3 %. The app's working card shows exactly this.

Solve for length

Switch “Solve for” to Max length and the same formula runs backwards: with 16 A on 2.5 mm² at 3 % you can go 24.3 m one way.

What this does not check. Current-carrying capacity (Iz) — use the ampacity or cable size calculator; loop impedance and disconnection time; short-circuit withstand; the run between the house connection and the meter. Lastsocket is a design aid. It does not replace the applicable installation standard, manufacturer data, or a qualified person’s judgement. Sources and limits →
Free or Pro. Typing a cross-section and reading the verdict is free, in every pack, with one "try the next size" tap on a FAIL. Finding the smallest cross-section automatically is Pro.

Questions

Why does the pack cite DIN 18015-1 and not DIN VDE 0100-520?

For homes, the figure German installers work to comes from DIN 18015-1, measured from the meter to the outlet, so that is the rule the app applies and cites.

Why is there one figure for every circuit?

Because the rule the pack applies does not split lighting from other circuits: 3 % for every circuit under DIN VDE 0100. Other packs have separate rows.

What about the cable before the meter?

That run has its own requirements from the network operator. The pack does not cover it; size it to the operator's rules.