BS 7671 voltage drop calculator

Enter the current, the one-way length and the cross-section; the calculator below returns the drop in volts and percent and a PASS or FAIL against 3 % for lighting and 5 % for other circuits on a public supply (6 % and 8 % on a private one) under BS 7671, with the Appendix 4 table cited under the number.

Limits and citations come from the app's pack files. The calculator below is checked against the app's engine on every build · engine 1, built 2026-11-14.

voltage drop 6.2 percent, fail, limit 5 percent other

14.2V
6.2%
FAIL
Over limit by 1.2 % · 215.8 V at the load
17.7 mV/A/m
BS 7671 Appendix 4 Table 4Ab — other 5 % (public supply)
Working
Resistance
r₂₀ = 7.410 Ω/km · Copper 2.5 mm² · IEC 60228 max DC
Temperature
θ = 70 °C (PVC 70 °C operating) · α = 0.00393 /K · rθ = 8.866 mΩ/m
Formula
ΔU = 2 · I · L · rθ · cos φ
Numbers
2.000 · 16.00 A · 50.0 m · 8.866 mΩ/m · 1.00 = 14.186 V
Percent
14.186 / 230 = 6.17 % · limit 5 % · BS 7671 (UK / IE) pack
Not checked
Iz · short-circuit · Zs / disconnection time
Engine
1

Design aid. Verify against your installation standard and manufacturer data.

Try it

Free tier · same numbers as the app
Solve for
System
m one-way
CSA
2.5 mm²
Conductor
Insulation
cos φ
Supply
Limit

Conductor at operating temperature (70 °C). Values commit when you leave a field, as in the app.

Same numbers. Offline. In your pocket.

In the app, one tap tries the next size.

The app does this in the van with no signal, keeps your last five jobs, and sizes the cable for you with Iz and voltage drop together.

Finding the smallest size for you is Pro. What Pro unlocks

Checked against the app's engine on every build · engine 1

The limits in the BS 7671 pack

Straight from the app's pack file. The citation is what the app prints under every result.

PackLightingOtherCited as
BS 7671 (UK / IE)3 % public · 6 % private5 % public · 8 % privateBS 7671 Appendix 4 Table 4Ab

How the app applies BS 7671

BS 7671 is the UK wiring standard, published by the IET and BSI. Its voltage drop limits sit in Appendix 4, and the app cites them by table: the line under every result names Table 4Ab and the row it used.

  • Two supply rows, two circuit rows. The pack holds lighting and other circuits, each for a public and a private supply. Pick the row that matches the job; the verdict and the citation follow it.
  • Operating temperature, not 20 °C. The conductor resistance is taken at the temperature the cable runs at under load, which is what the tables assume. A calculation at 20 °C under-reads the drop and can pass a cable that fails.
  • mV/A/m on the working card. The figure UK electricians size from is shown, derived from that same resistance, so the app’s working reads like the book’s table.
  • A custom limit is one tap away when a specification asks for less than the table.

The figures and citations on this page come from the app’s BS 7671 pack file, the same file the app reads on site.

Worked example

System230 V single-phase
Load16 A
Length, one way50 m
Cross-section2.5 mm² copper, PVC at 70 °C
LimitBS 7671 Appendix 4 Table 4Ab — other 5 % (public supply)

r20 for 2.5 mm² is 7.41 Ω/km; at 70 °C that is 8.87 mΩ/m. ΔU = 2 × 16 × 50 × 0.00887 = 14.19 V, which is 6.17 % of 230 V. FAIL at 5 %, over by 1.2 %, with 215.8 V at the load. One size up, 4 mm², comes to 3.8 %. The app's working card shows exactly this.

Solve for length

Switch “Solve for” to Max length and the same formula runs backwards: with 16 A on 2.5 mm² at 5 % you can go 40.5 m one way.

What this does not check. Current-carrying capacity (Iz) — use the ampacity or cable size calculator; earth fault loop impedance (Zs) and disconnection time; short-circuit withstand; the drop on the supply side of the origin. Lastsocket is a design aid. It does not replace the applicable installation standard, manufacturer data, or a qualified person’s judgement. Sources and limits →
Free or Pro. Typing a cross-section and reading the verdict is free, in every pack, with one "try the next size" tap on a FAIL. Finding the smallest cross-section automatically is Pro.

Questions

Public or private supply — which row do I pick?

Public, when the installation is fed directly from the distribution network; private, when it has its own transformer or generator. 3 % for lighting and 5 % for other circuits on a public supply (6 % and 8 % on a private one) under BS 7671. The app prints the row it used under every result.

Where are the mV/A/m figures?

On the working card. The BS 7671 pack shows the mV/A/m figure next to the conductor resistance it is derived from, at the conductor's operating temperature, so you can set it against the table in your edition.

Does the limit apply to the final circuit alone?

No. Appendix 4 sets the drop from the origin of the installation to the equipment, so a sub-main and the final circuit it feeds share one budget. Work out each run and add them.

Does it check Zs or disconnection times?

No. The app checks voltage drop and, in the cable size calculator, current-carrying capacity. Earth fault loop impedance and disconnection times stay with you and your edition of the book.