IEC 60364 voltage drop calculator

Enter the current, the one-way length and the cross-section; the calculator below returns the drop in volts and percent and a PASS or FAIL against 3 % for lighting and 5 % for other circuits under IEC typical, with IEC 60364-5-52 clause 525 cited under the number.

Limits and citations come from the app's pack files. The calculator below is checked against the app's engine on every build · engine 1, built 2026-11-14.

voltage drop 6.2 percent, fail, limit 5 percent other

14.2V
6.2%
FAIL
Over limit by 1.2 % · 215.8 V at the load
IEC 60364-5-52 cl. 525 — voltage drop, other circuits 5 %
Working
Resistance
r₂₀ = 7.410 Ω/km · Copper 2.5 mm² · IEC 60228 max DC
Temperature
θ = 70 °C (PVC 70 °C operating) · α = 0.00393 /K · rθ = 8.866 mΩ/m
Formula
ΔU = 2 · I · L · rθ · cos φ
Numbers
2.000 · 16.00 A · 50.0 m · 8.866 mΩ/m · 1.00 = 14.186 V
Percent
14.186 / 230 = 6.17 % · limit 5 % · IEC typical pack
Not checked
Iz · short-circuit · Zs / disconnection time
Engine
1

Design aid. Verify against your installation standard and manufacturer data.

Try it

Free tier · same numbers as the app
Solve for
System
m one-way
CSA
2.5 mm²
Conductor
Insulation
cos φ
Limit

Conductor at operating temperature (70 °C). Values commit when you leave a field, as in the app.

Same numbers. Offline. In your pocket.

In the app, one tap tries the next size.

The app does this in the van with no signal, keeps your last five jobs, and sizes the cable for you with Iz and voltage drop together.

Finding the smallest size for you is Pro. What Pro unlocks

Checked against the app's engine on every build · engine 1

The limits in the IEC typical pack

Straight from the app's pack file. The citation is what the app prints under every result.

PackLightingOtherCited as
IEC typical3 %5 %IEC 60364-5-52 cl. 525

How the app applies IEC 60364

IEC 60364 is the international series for low-voltage installations; NEN 1010, NF C 15-100, the DIN VDE 0100 series and many other national standards are built on it. Voltage drop is part 5-52, clause 525, and the app’s IEC pack cites it by clause: the line under every result names clause 525 and the row it used.

  • The common figures. The pack holds lighting and other circuits for a supply from the public network, the figures most national standards start from.
  • Operating temperature, not 20 °C. The conductor resistance is taken at the temperature the cable runs at under load: 70 °C for PVC, 90 °C for XLPE. A calculation at 20 °C under-reads the drop and can pass a cable that fails.
  • Single-phase and three-phase. 230 V single-phase and 400 V three-phase, plus DC for 12, 24 and 48 V work.
  • A custom limit is one tap away when your national figure differs.

The figures and citations on this page come from the app’s IEC pack file, the same file the app reads on site.

Worked example

System230 V single-phase
Load16 A
Length, one way50 m
Cross-section2.5 mm² copper, PVC at 70 °C
LimitIEC 60364-5-52 cl. 525 — voltage drop, other circuits 5 %

r20 for 2.5 mm² is 7.41 Ω/km; at 70 °C that is 8.87 mΩ/m. ΔU = 2 × 16 × 50 × 0.00887 = 14.19 V, which is 6.17 % of 230 V. FAIL at 5 %, over by 1.2 %, with 215.8 V at the load. One size up, 4 mm², comes to 3.8 %. The app's working card shows exactly this.

Solve for length

Switch “Solve for” to Max length and the same formula runs backwards: with 16 A on 2.5 mm² at 5 % you can go 40.5 m one way.

What this does not check. Current-carrying capacity (Iz) — use the ampacity or cable size calculator; loop impedance and disconnection time; short-circuit withstand; any figure your national standard sets differently. Lastsocket is a design aid. It does not replace the applicable installation standard, manufacturer data, or a qualified person’s judgement. Sources and limits →
Free or Pro. Typing a cross-section and reading the verdict is free, in every pack, with one "try the next size" tap on a FAIL. Finding the smallest cross-section automatically is Pro.

Questions

When should I use the IEC pack?

When your national rules follow IEC 60364 and the app has no pack of their own. Check the figure in your national standard; if it differs, type it as a custom limit and the verdict follows it.

Why is it called "IEC typical"?

Because IEC 60364-5-52 gives these values as recommendations that national standards adopt or change. The pack holds the common figures for a supply from the public network: 3 % for lighting and 5 % for other circuits under IEC typical.

Does the limit apply to the final circuit alone?

No. Clause 525 sets the drop from the origin of the installation to the equipment, so a sub-main and the final circuit it feeds share one budget. Work out each run and add them.

Other standards

The voltage drop page: formula, operating temperature, and every pack side by side →